Mechanical installation
Wall mounting
l
96
EDK82MV371 DE/EN/FR 7.0
EMC−compliant wiring
Conditions for trouble−free operation:
ƒ Except for the mains cable, use shielded cables only.
ƒ Carefully connect the shielding to PE.
ƒ Separate control and mains cables from motor cable!
ƒ Connect motor and mains PE conductors to separate PE terminals.
Fig. 4−1
Fig. 4−2
A
B
F
G
D
C
E
H
8200mot169
X1
X2
Shield connection:
1. Prepare the cable
2. Insert the cable tie
3. Lay the cable into the
cable tie and tighten it.
The shield must be
tightly connected to
the shield sheet.
0
Mains cable L1, N, PE or L1, L2, PE
1
PE connection for mains cable
2
Shield connection, motor cable; fix the shield tightly to the sheet with the cable tie
3
Use shielded motor cable (use low−capacitance motor cables)
4
PE connection of motor cable
5
Shield connection, control cable ( fix the shield tightly to the sheet with the cable tie)
6
Shielded control cable
7
Function module
X1
Terminal strip mains connection
X2
Terminal strip motor connection
PES
HF shield connection by large surface connection to PE