96) or motor emc screw, X1 x2, Mechanical installation – Lenze E82MVxxx 2Bxxx User Manual

Page 96

Advertising
background image

Mechanical installation

Wall mounting

4

l

96

EDK82MV371 DE/EN/FR 7.0

EMC−compliant wiring
Conditions for trouble−free operation:

ƒ Except for the mains cable, use shielded cables only.
ƒ Carefully connect the shielding to PE.
ƒ Separate control and mains cables from motor cable!
ƒ Connect motor and mains PE conductors to separate PE terminals.

Fig. 4−1

Fig. 4−2

A

B

F

G

D

C

E

H

8200mot169

X1

X2

Shield connection:
1. Prepare the cable

2. Insert the cable tie

3. Lay the cable into the

cable tie and tighten it.
The shield must be
tightly connected to
the shield sheet.

0

Mains cable L1, N, PE or L1, L2, PE

1

PE connection for mains cable

2

Shield connection, motor cable; fix the shield tightly to the sheet with the cable tie

3

Use shielded motor cable (use low−capacitance motor cables)

4

PE connection of motor cable

5

Shield connection, control cable ( fix the shield tightly to the sheet with the cable tie)

6

Shielded control cable

7

Function module

X1

Terminal strip mains connection

X2

Terminal strip motor connection

PES

HF shield connection by large surface connection to PE