Troubleshooting and fault elimination – Lenze E82MVxxx 2Bxxx User Manual
Page 136
Advertising
Troubleshooting and fault elimination
Fault messages
l
136
EDK82MV371 DE/EN/FR 7.0
Remedy
Cause
Fault
PC
1)
Keypad
Pr5
a
79
Internal fault
EEPROM is defective
Contact Lenze
Pt5
a
81
Time error
during
parameter set
transfer
Data flow from keypad or PC
interrupted, e.g. keypad has
been removed during data
transmission
Before enabling the controller,
repeat the data transfer or load
the Lenze setting.
rSt
a
76
Error during
Auto−TRIP reset
More than 8 error messages
within 10 minutes
Dependent on the error
message
sd5
a
85
Wire breakage,
analog input 1
Current on analog input
< 4 mA for setpoint range
4 ... 20 mA
Close the circuit at the analog
input
sd7
a
87
Wire breakage,
analog input 2
1)
LECOM error number, display in Global Drive Control (GDC) parameter setting program