Linear v/f-characteristic control, Linear v/f−characteristic control, Commissioning – Lenze E82MVxxx 2Bxxx User Manual

Page 111

Advertising
background image

Commissioning

Linear V/f−characteristic control

7

l

111

EDK82MV371 DE/EN/FR 7.0

Linear V/f−characteristic control

The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.

Switch−on sequence

Comment

1.

Connect keypad

2.

Ensure that controller inhibit is active after mains
connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.

The keypad is in "Disp" mode after approx. 2 s and
indicates the output frequency (C0050)

The USEr menu is active

5.

Change to the

f mode to configure the basic

settings for your drive

Blinking on the display: 0050

6.

Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O
to the same range (see Mounting
Instructions for the standard I/O)

7.

Adapt the terminal configuration to the wiring
(C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: Depending on the controller type

The Lenze setting is suitable for all
common applications