Technical data, General data and operating conditions, 3 technical data – Lenze E82MVxxx 2Bxxx User Manual

Page 84

Advertising
background image

Technical data

General data and operating conditions

3

l

84

EDK82MV371 DE/EN/FR 7.0

3

Technical data

General data and operating conditions

Conformity and approval

Conformity

CE

2006/95/EC

Low−Voltage Directive

2004/108/EG

EMC Directive

Approval

UL

UL 508C

Underwriter Laboratories (File No. E132659)
Power Conversion Equipment

CSA

22.2 No. 14

GOST−R

51321.1−2000 No. POCC DE.AN30.Bo8845
51321.3−99

Protection of persons and equipment

Type of protection

IEC/EN60529
NEMA 250 / UL50

IP55 without protective cap on the AIF interface,
protection against accidental contact according to
type 12

IEC/EN60529
NEMA 250 / UL50

IP65 with protection cover on the AIF interface,
protection against accidental contact according to type 4

Earth leakage current

IEC/EN 61800−5−1

> 3.5 mA AC
> 10 mA DC

Observe regulations and
safety instructions!

Insulation of control
circuits

IEC/EN 61800−5−1

Safe mains isolation by double (reinforced) insulation

Insulation strength

IEC/EN 61800−5−1

Overvoltage category III for site altitude

£ 2000 m

Overvoltage category II for site altitude > 2000 m

Protective measures

Short circuit, short to earth (protected against short to earth during operation,
limited protection against short to earth on powerup), overvoltage, motor
stalling, motor overtemperature (input for PTC or thermal contact, I

2

t

monitoring)