Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

11

Logic In 1

An input is programmed as Logic In 1 and is active.

12

Logic In 2

An input is programmed as Logic In 2 and is active.

13

Logic In 1 & 2

Both Logic inputs are programmed and active.

14

Logic In 1 or 2

One or both Logic inputs are programmed and one or both is active.

15

StpLogic Out

Drive enters Step Logic step with Digit 3 of Command Word (Parameters 240…247).

16

Timer Out

Timer has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.

17

Counter Out

Counter has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.

18

Above PF Ang

Power factor angle has exceeded the value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto
Output 2 Level). Use Parameter 159 or 162 to set threshold.

19

Anlg In Loss

Analog input loss has occurred. Program parameter 122 (Analog In Los) for desired action when loss occurs

20

ParamControl

Enables the output to be controlled over the network communications by writing to Parameter 159 (Opto Out 1
Level) or Parameter 162 (Opto Output 2 Level) (0 = Off, 1 = ON).

21

NonRec Fault

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

22

EM Brk Cntrl

EM Brake is energized. Program Parameter 260 (EM Brk Off Delay) and Parameter 262 (EM Brk On Delay) for
desired action.

159 (Opto Out1 Level)
162 (Opto Out2 Level)
Sets the trip point for the digital output relay if the value of Parameter 158 (Opto
Out1 Sel) or Parameter 161 (Opto Out2 Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.

Parameter Number

159 162

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0.0

Maximum Value

9999

Default Value

0.0

Options

Description

ATTENTION

!

Parameter 192 (Auto Rstrt Tries) is not enabled. A non-
resettable fault has occurred.

Parameters 158 and 161

Setting

Parameters 159 and 161

Min./Max.

6

0/400 Hz

7

0/180%

8

0/815V

10

0/100%

16

0.1/9999 sec

17

1/9999 counts

18

1/180

°

20

0/1