Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

4-5

➊ Indicates DB1 Comm Fault for Bulletin 284.

Trip Status
This parameter provides trip identification.

Parameter Number

4

Access Rule

GET

Data Type

WORD

Group

DeviceLogix

Units

Minimum Value

0

Maximum Value

65535

Default Value

0

Bit

Function

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Short Circuit

X

Overload

X

Phase Short

X

Ground Fault

X

Stall

X

Control Power

X

IO Fault

X

Overtemperature

X

Over Current

X

Dnet Power Loss

X

Internal Comm

X

DC Bus Fault

X

EEprom

X

HW Fault

X

Restart Retries

X

Misc. Fault