11-4

Troubleshooting

Table 11.2 Motor Will Not Start – No Output Voltage to the Motor

Table 11.3 Motor Will Not Start – No Output Voltage to the Motor

Table 11.4 Motor Rotates (but does not accelerate to full speed)

Table 11.5 Motor Stops While Running

LED Status Indication

Possible Cause

Possible Solutions

Fault or Network Status Led indicates a
fault condition

See Fault Description

See Table 11.1 and/or Table 11.16 addressing fault
conditions

No Fault condition indicated

Three Phase is absent

Check power system.
Check three-phase power wiring and correct if
necessary

Display is blank

Control voltage is absent

Check control wiring and polarity. Correct if
necessary.

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 11.12 addressing fault conditions

Display is blank

Control voltage is absent

Check control wiring and proper polarity. Correct if
necessary

Starting

Two or three power phases are missing

Check power system

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 11.12 addressing fault conditions

Starting

Mechanical problems
Inadequate Current Limit setting
Failed control module

Check for binding or external loading and correct
Check motor
Adjust the Current Limit level to a higher setting
Replace control module

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 11.12 addressing fault conditions

RUN LED is blank

Control voltage is absent
Failed control module

Check control wiring and correct if necessary
Replace control module

Starting

Two or three power phases are missing
Failed control module

Check power system
Replace control module