This chapter provides a brief overview of the features and
functionality of the Bulletin 280/281 and 284 ArmorStart®
Distributed Motor Controllers.

Description

The ArmorStart Distributed Motor Controllers are integrated, pre-
engineered, starters with Bulletin 280/281 for full-voltage and
reversing applications and Bulletin 284 for variable frequency AC
drives applications. The ArmorStart offers a robust IP67/NEMA Type
4 enclosure design, which is suitable for water wash down
environments.

The modular “plug and play” design offers simplicity in wiring the
installation. The quick disconnects for the I/O, communications, and
motor connections reduce the wiring time and eliminate wiring errors.
The ArmorStart offers, as standard, four DC inputs and two relay
outputs, to be used with sensors and actuators respectively, for
monitoring and controlling the application process. The ArmorStart’s
LED status indication and built-in diagnostics capabilities allow ease
of maintenance and troubleshooting. The optional Hand/Off/Auto
(HOA) keypad configuration allows local start/stop control at the
ArmorStart

Distributed Motor Controller.

The ArmorStart Distributed Motor Controller offers short circuit
protection per UL508 and IEC 60947. The ArmorStart is rated for
local-disconnect service by incorporating the Bulletin 140 Motor
Protector as the local-disconnect, eliminating the need for additional
components. The ArmorStart Distributed Motor Controllers are
suitable for group motor installations.

Safety ArmorStart

The safety version of the ArmorStart provides a safety solution
integrated into DeviceNet Safety installations. The Bulletin 280/281/
284 Safety ArmorStart achieves Category 4 functionality by using
redundant contactors. The Safety ArmorStart offers a quick connects
via the gland plate to the 1732DS-IB8XOBV4 safety I/O module. The
Bulletin 1732DS Safety I/O inputs will monitor the status of the
safety rated contactors inside the ArmorStart. The Bulletin 1732DS
Safety I/O outputs to provide 24V DC power for control power to the
ArmorStart.

Note: The Bulletin 280/281/284 Safety ArmorStart is suitable for

safety applications up to Safety Category 4PL e (TÜV
assessment per ISO 13849-1:2008). T

Ü

V compliance letter is

available upon request.

Note: For additional information regarding the

1732DS-IB8XOBV4 safety I/O module, see publication
1791DS-UM001*-EN-P.