Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual

Page 106

Advertising
background image

4-36

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

Table 4.5

Analog Output Options

Note: Only output range 0…10V applies with the factory installed
A10 option.

Options 5…14, 16, 17, 19, and 20 are not valid options.

Analog Out Sel
Sets the analog output signal (0…10V). The output is used to provide a signal that is
proportional to several drives

Parameter Number

165

Related Parameters

135, 166

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

See Table for details

Minimum Value

Maximum Value

Default Value

Options

Output Range

Minimum Output

Value

Maximum Output Value A066

(Analog Out High)

DIP Switch Position

Related

Parameter

0

OutFreq 0…10

0…10V

0V = 0 Hz

P035 (Maximum Freq)

0…10V

101

1

OutCurr 0…10

0…10V

0V = 0 Amps

200% Drive Rated Output Current

0…10V

103

2

OutVolt 0…10

0…10V

0V = 0 Volts

120% Drive Rated Output Volts

0…10V

104

3

OutPowr 0…10

0…10V

0V = 0 kW

200% Drive Rated Power

0…10V

122

4

TstData 0…10

0…10V

0V = 0000

65535 (Hex FFFF)

0…10V

119

5

OutFreq 0…20

0…20 mA

0 mA = 0 Hz

P035 (Maximum Freq)

0…20 mA

101

6

OutCurr 0…20

0…20 mA

0 mA = 0 Amps

200% Drive Rated Output Current

0…20 mA

103

7

OutVolt 0…20

0…20 mA

0 mA = 0 Volts

120% Drive Rated Output Volts

0…20 mA

104

8

OutPowr 0…20

0…20 mA

0 mA = 0 kW

200% Drive Rated Power

0…20 mA

122

9

TstData 0…20

0…20 mA

0 mA = 0000

65535 (Hex FFFF)

0…20 mA

119

10

OutFreq 4…20

4…20 mA

4 mA = 0 Hz

P035 (Maximum Freq)

0…20 mA

101

11

OutCurr 4…20

4…20 mA

4 mA = 0 Amps

200% Drive Rated Output Current

0…20 mA

103

12

OutVolt 4…20

4…20 mA

4 mA = 0 Volts

120% Drive Rated Output Volts

0…20 mA

104

13

OutPowr 4…20

4…20 mA

4 mA = 0 kW

200% Drive Rated Power

0…20 mA

122

14

TstData 4…20

4…20 mA

4 mA = 0000

65535 (Hex FFFF)

0…20 mA

119

15

OutTorq 0…10

0…10V

0V = 0 Amps

200% Drive Rated FLA

0…10V

129

16

OutTorq 0…20

0…20 mA

0 mA = 0 Amps

200% Drive Rated FLA

0…20 mA

129

17

OutTorq 4…20

4…20 mA

4 mA = 0 Amps

200% Drive Rated FLA

0…20 mA

129

18

Setpnt 0…10

0…10V

0V = 0%

100.0% Setpoint Setting

0…10V

209

19

Setpnt 0…20

0…20 mA

0 mA = 0%

100.0% Setpoint Setting

0…20 mA

209

20

Setpnt 4…20

4…20 mA

4 mA = 0%

100.0% Setpoint Setting

0…20 mA

209

Analog Out High
Scales the maximum output value for parameter 165 source setting

Parameter Number

166

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

%

Minimum Value

0%

Maximum Value

800%

Default Value

100%