Product Overview

1-5

LED Status Indication

The LED Status Indication provides 4 status LEDs and a Reset
button. The LEDs provide status indication for the following:

POWER LED
The LED is illuminated solid green when control power is present
and with the proper polarity

RUN LED
This LED is illuminated solid green when a start command and
control power are present

NETWORK LED
This bi-color (red/green) LED indicates the status of the
communication link

FAULT LED
Indicates Controller Fault (Trip) condition

The “Reset Button” acts as a local trip reset.

Figure 1.3 Status Indication and Reset

Fault Diagnostics

Fault diagnostics capabilities built in the ArmorStart Distributed
Motor Controller help you pinpoint a problem for easy
troubleshooting and quick re-starting.

Fault Indication

Available on

Bulletin:

Fault Indication

Available on

Bulletin:

280/281

284

280/281

284

Short Circuit

X

X

Phase Imbalance

X

Overload

X

X

Miscellaneous Fault

X

X

Phase Loss

X

X

Brake Fuse Detection

X

Control Power Loss

X

X

Internal Comm. Fault

X

Control Power Fuse Detection

X

X

DC Bus Fault

X

Output Power Fuse Detection

X

X

Ground Fault

X

I/O Fault

X

X

Overcurrent

X

Over Temperature

X

X

Restart Retries

X

DeviceNet™ Power Loss

X

X

Stall

X

EEprom Fault

X

X

Phase Short

X

Hardware Fault

X

X