Diagnostics

Clear Fault

You may clear a fault using the following methods:

Remotely via network communications

A remote reset will be attempted upon detection of a rising edge
(0 to 1 transition) of the “Fault Reset” bit in the various I/O
assemblies. A remote reset will also be attempted upon detection
of the rising edge of the “Fault Reset” parameter.

Locally via the “Reset” button on the LED Status indication
keypad.

Fault Codes

Table 10.1 provides a complete reference of the Fault LED
indications for Bulletin 280 and 281 ArmorStart Distributed Motor
Controllers.

Table 10.1 Fault Indication

Blink Pattern

Fault Types

Bulletin 280/281

Bulletin 284

1

Short Circuit

Short Circuit

2

Overload Trip

Overload Trip

3

Phase Loss

Phase Short

4

Reserved

Ground Fault

5

Reserved

Stall

6

Control Power

Control Power

7

I/O Fault

I/O Fault

8

Over Temperature

Over Temperature

9

Phase Imbalance

Over Current

10

DeviceNet™ Power Loss

DeviceNet™ Power Loss

11

Reserved

Internal Communications

12

Reserved

DC Bus Fault

13

EEPROM Fault

EEPROM Fault

14

Hardware Fault

Hardware Fault

15

Reserved

Restart Retries

16

Reserved

Misc. Fault