Troubleshooting

11-19

Base Module Replacement
(Bulletin 280/281)

Installation of Base Module

1) Mount Base Module with four mounting screws.

2) Re-install conduit fittings and wires onto terminal block.

3) Tighten the terminal screws.

4) Install terminal cover plate.

5) Tighten four mounting screws on the terminal access cover plate.

6) Install Control Module.

7) Tighten the four mounting screws.

8) Install motor cable, comunication cables and all others connected
to the inputs and outputs.

Figure 11.4 Bulletin 280/281 Base Module Installation

ATTENTION

!

To avoid shock hazard, disconnect main power
before working on the controller, motor, or control
devices

4

3

1

2

46 - 50 lb-in

7

7

6

5

Base Module

Input/
Output
Cable

Communication
Cable

Motor Cable

Control Module

Terminal Access
Cover Plate

Base
Module

12 lb - in./1.36 Nm