Safety i/o module and tüv requirements, Appendix – Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual

Page 289

Advertising
background image

Appendix

E

Safety I/O Module and TÜV Requirements

ArmorStart Safety-Related Parts

Each ArmorStart Safety Distributed motor controller is intended to be
combined with the 1732DS-IB8XOBV4 safety I/O module to form a
subsystem that is part of the overall machine stop function. The motor
controllers are connected to the safety I/O module through specified
cable assemblies. The combination of one of these controllers, the
safety module, and the specified interconnecting cables are referred to
as the ArmorStart Safety-Related Parts. The part numbers for each of
these components is specified below. The combination of these
components is shown in Figure E.1. The safety I/O module and PLC
program must be configured as outlined. See configuration of Safety
I/O Module and PLC program.

Table E.1

Safety-Related Parts

Catalog Number

Description

280…S*

* - denotes safety version of Bulletin 280

Bulletin 280 Distributed Motor Controller –
controller is full-voltage, non-reversing

281…S*

* - denotes safety version of Bulletin 280

Bulletin 281 Distributed Motor Controller –
controller is full-voltage, reversing

284…S*

* - denotes safety version of Bulletin 280

Bulletin 281 Distributed Motor Controller –
controller is variable-frequency AC drive

1732DS-IB8XOBV4

Guard I/O DeviceNet Safety Module

889D-F4HJDM-*, 889D-F4AEDM-*
or equivalent

* - denotes length

SM cable assembly - Interconnecting
cable assembly between safety
module input and ArmorStart
controller connector labeled “SM”.
Assembly provides contactor position
feedback.

A1/A2 cable assembly -
Interconnecting cable assembly
between safety module output and
ArmorStart controller connector
labeled “A1/A2”. Assembly provides
output contactor coil power and
controller power supply.

Advertising