Installation and Wiring

2-15

Wiring

Power and Ground Wiring

Table 2.1 provides the power and ground wire capacity and the
tightening torque requirements. The power and ground terminals will
accept a maximum of two wires per terminal.

Table 2.1

Power and Ground Wire, Size and Torque Specifications

Terminal Designations

As shown in the next figures, the ArmorStart

Distributed Motor Controller

contains terminals for power, control, safety monitor inputs, and ground
wiring. Access can be gained by removing the terminal access cover plate.

Figure 2.1 Bulletin 280 Power, Control, and Safety Monitor Input Terminals

Terminals

Wire Size

Torque

Wire Strip Length

Power

and

Ground

Primary Terminal:

1.3…5.3 mm

2

(#16 …#10 AWG)

Secondary Terminal:

0.8…5.3 mm

2

(#18 …#10 AWG)

Primary Terminal:

10.8 lb•in
(1.2 N•m)

Secondary Terminal:

4.5 lb•in

(0.5 N•m)

0.35 in. (9 mm)