Specifications

A-5

Bulletin 284

Electrical Ratings

UL/NEMA

IEC

Power Circuit

Rated Operation Voltage

380Y/220…480Y/277V AC

380Y/220…480Y/277V AC

Rate Insulation Voltage

600V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

2200V AC

2500V AC

Operating Frequency

50/60 Hz

Utilization Category

N/A

AC-3

Protection Against Shock

N/A

IP2X

Short Circuit
Protection

SCPD Performance

Sym. Amps RMS @ 480Y/277V

Current Rating

10 A

65 kA

25 A

30 kA

SCPD List

Size per NEC Group Motor

Control
Circuit

Rated Operation Voltage

24V DC (+10%, -15%) A2 (should be grounded at voltage source)

Rate Insulation Voltage

250V

250V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

1500V AC

2000V AC

Overvoltage Category

III

Operating Frequency

50/60 Hz

50/60 Hz

Power Requirements

Units

No Options

Brake or Output Contactor

With Brake and Output Contactor

Control Voltage

Volts

24V DC

24V DC

24V DC

Total Control (Pick Up)

VA (W)

(11.0 W)

(13.0 W)

(16.0 W)

Total Control (Hold In)

VA (W)

(11.0 W)

(13.0 W)

(16.0 W)

External Devices powered by Control Voltage

Outputs (2) 1 A max. each

Amps

2

2

2

Total Control VA (Pick Up) with max. outputs

VA (W)

(59.0 W)

(61.0 W)

(64.0 W)

Total Control VA (Hold In) with max. outputs

VA (W)

(59.0 W)

(61.0 W)

(64.0 W)

Input Ratings

Rated Operation Voltage

24V DC

Input On-State Voltage Range

10…26V DC

Input On-state Current

3.0 mA @ 10V DC

7.2 mA @ 24V DC

Input Off-state Voltage Range

0…5V DC

Input Off-state Current

<1.5 mA

Input Filter — Software Selectable

Off to On

Settable from 0…64 ms in 1 ms increments

On to Off

Settable from 0…64 ms in 1 ms increments

Input Compatibility

N/A

IEC 1+

Number of inputs

4

Sensor Source

Voltage Status Only

11…25V DC from DeviceNet™

Current Available

50 mA MAX per Input, 200 mA Total

Output Ratings (Sourced
from Control Circuit)

Rated Operation Voltage

240V AC / 30V DC

240V AC / 30V DC

Rate Insulation Voltage

250V

250V

Dielectric Withstand

1500V AC

2000V AC

Operating Frequency

50/60 Hz

50/60 Hz

Type of control circuit

Electromechanical Relay

Kind of Current

AC/DC

Conventional Thermal Current I

th

Total of both outputs

2 A

Type of Contacts

Normally Open (N.O.)

Number of Contacts

2