Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

4-57

Parameters 240…247 are only active if 138 (Speed Reference) is set
to 6 Stp Logic.

These parameters can be used to create a custom profile of frequency
commands. Each step can be based on time, status of a Logic input, or
a combination of time and the status of a Logic input.

Digits 0…3 for each (Stp Logic x) parameter must be programmed
according to the desired profile.

A Logic input is established by setting a digital input, Parameters
151…154 (Digital Inx Sel), to 23 Logic In1 and/or 24 Logic In2.

A time interval between steps can be programmed using Parameters
250…257 (Stp Logic Time x). See Table 4.8 for related parameters.

The speed for any step is programmed using Parameters 170…177
(Preset Freq x).

PID Deadband
Sets the lower limit of the PID output.

Parameter Number

238

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1%

Minimum Value

0.0%

Maximum Value

10.0%

Default Value

0.0%

PID Preload
Sets the value used to preload the integral component on start or enable.

Parameter Number

239

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.0 Hz

Minimum Value

0.0 Hz

Maximum Value

400.0 Hz

Default Value

0.0 Hz

A240 (Stp Logic 0)
A241 (Stp Logic 1)
A242 (Stp Logic 2)
A243 (Stp Logic 3)
A244 (Stp Logic 4)
A245 (Stp Logic 5)
A246 (Stp Logic 6)
A247 (Stp Logic 7)

Parameter Number

240…247

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0001

Maximum Value

baFF

Default Value

00F1

Stop drive before changing this parameter.