Specifications

A-7

Bulletin 284, Continued

IP67 Dynamic Brake Resistor Ratings

Table A.1 IP67 Dynamic Brake Resistor

* - Indicates cable length (0.5 m or 1.0 m).
Note: Always check the resistor ohms against minimum resistance for drive being used.
Note: Duty Cycle listed is based on full speed to zero speed deceleration. For constance regen at full speed, duty cycle capability is half of what is listed. Application Type 1
represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum
of 150%.

Figure A.9 Dynamic Brake Resistor

Line Voltage

Frequency

3-Phase kW Rating

3-Phase Hp Rating

Output Current (A)

Input Current (A)

Drive Ratings

380

50

0.4

1.4

2.15

0.75

2.3

3.80

1.5

4.0

6.40

2.2

6.0

9.00

3.0

7.6

12.40

460

60

0.5

1.4

1.85

1

2.3

3.45

2

4.0

5.57

3

6.0

8.20

5

7.6

12.5

Application Type 1

Application Type 2

Drive and

Motor Size

kW

Part Number

Resistance

Ohms ± 5%

Continuous

Power kW

Max Energy

kJ

Max

Braking

Torque % of

Motor

Braking

Torque % of

Motor

Duty

Cycle %

Braking

Torque % of

Motor

Duty

Cycle %

400-480 Volt AC Input Drives

0.37 (0.5)

284R-360P500-M*

360

0.086

17

305%

100%

47%

150%

31%

0.75 (1)

284R-360P500-M*

360

0.086

17

220%

100%

23%

150%

15%

1.5 (2)

284R-360P500-M*

360

0.086

17

110%

100%

12%

110%

11%

2.2 (3)

284R-120P1K2-M*

120

0.26

52

197%

100%

24%

150%

16%

4 (5)

284R-120P1K2-M*

120

0.26

52

124%

100%

13%

124%

10%

H

J

F

C

G

B
D