Troubleshooting

Table 11.12 Motor and/or Drive Will Not Accelerate to Commanded Speed

Table 11.13 Motor Operation is Unstable

Table 11.14

Drive Will Not Reverse Motor Direction

Cause(s)

Indication

Corrective Action

Acceleration time is
excessive.

None

Reprogram Parameter 139 (Accel Time 1) or Parameter
167 (Accel Time 2).

Excess load or short
acceleration times
force the drive into
current limit,
slowing, or stopping
acceleration.

None

Compare Parameter 103 (Output Current) with
Parameter 189 (Current Limit1).

Remove excess load or reprogram Parameter 139
(Accel Time 1) or Parameter 167

(Accel Time 2).

Check for improper setting of Parameter 184 (Boost
Select).

Speed command
source or value is not
as expected.

None

Verify Parameter 102 (Commanded Freq).

Check Parameter 112 (Control Source) for the proper
Speed Command.

Programming is
preventing the drive
output from
exceeding limiting
values.

None

Check Parameter 135 (Maximum Freq) to insure that
speed is not limited by programming.

Torque performance
does not match
motor
characteristics.

None

Set motor nameplate full load amps in Parameter
226 (Motor NP FLA).

Use Parameter 227 (Autotune) to perform Static
Tune
or Rotate Tune procedure.

Set Parameter 225 (Torque Perf Mode) to
option 0V/Hz.

Cause(s)

Indication

Corrective Action

Motor data
was
incorrectly
entered.

None

1.

Correctly enter motor nameplate data into Parameters 131,
132, and 133.

2.

Enable Parameter 197 (Compensation).

3.

Use Parameter 184 (Boost Select) to reduce boost level.

Cause(s)

Indication

Corrective Action

Digital input is not selected for
reversing control.

None

Check (Digital Inx Sel). Choose correct input and
program for reversing mode.

Motor wiring is improperly
phased for reverse.

None

Switch two motor leads.

Reverse is disabled.

None

Check Parameter 195 (Reverse Disable).