Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual

Page 168

Advertising
background image

9-4

ArmorStart® ZIP Configuration

The “Zone Mask” parameters (parameters 78-81) select individual
bytes within a consumed message for placement in the DeviceLogix
Data Table. Each single bit in the mask represents a corresponding
byte in the consumed message packet. For example, consider an
ArmorStart that has zone 1 configured to consume data from another
ArmorStart that is producing data of the following format:

The user can choose to place only bytes 1 and 2 of the above
consumed data in the DeviceLogix Data Table by selecting a Zone
Mask value of 00000011 binary as shown in the following
RSNetWorx for DeviceNet screen:

The “Zone Offset” parameters (parameters 82-85) determine where in
the DeviceLogix Data Table to place the consumed data bytes chosen
for mapping. The “Zone Offset” value corresponds to a byte in the
DeviceLogix Data Table where the data should be placed. Continuing
our example from above, a value of 2 in the “Zone #1 Offset”
parameter would result in the masked consumed data bytes being
placed starting at byte 2 in the data table. This would result in the
following ZIP bit assignments:

ZIP 16 = Zone 1: Tripped
ZIP 17 = Zone 1: Warning

Instance 163 Standard Produced Starter with Network Outputs and ZIP CCV

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

1

Ready

Running Rev Running Fwd Warning

Tripped

2

140M On

HOA

User In 4

User In 3

User In 2

User In 1

3

Net Out 8

Net Out 7

Net Out 6

Net Out 5

Net Out 4

Net Out 3

Net Out 2

Net Out 1

4

Net Out 15 Net Out 14 Net Out 13 Net Out 12 Net Out 11 Net Out 10

Net Out 9

5

Device Value Key (low)

6

Device Value Key (high)

Advertising