H-6

PID Setup

3. At this point, the differential gain may not be needed. However, if

after determining the values for Parameter 234 (PID Prop Gain)
and Parameter 235 (PID Integ Time):

Response is still slow after a step change, increase Parameter
236 (PID Diff Rate).

Response is still unstable, decrease Parameter 236 (PID Diff
Rate).

The following figures show some typical responses of the PID loop at
different points during adjustment of the PID Gains.

Figure H.1 Unstable

Figure H.2 Slow Response — Over-Damped

Figure H.3 Oscillation — Under-Damped

Figure H.4 Good Response — Critically Damped

PID Feedback

PID Reference

Time

PID Feedback

PID Reference

Time

PID Feedback

PID Reference

Time

PID Feedback

PID Reference

Time