Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual

Page 232

Advertising
background image

B-12

Bulletin 280/281 CIP Information

Instance 4 is the Predefined Group 2 Connection Set Change of State/
Cyclic I/O Message Connection. The following instance 4 attributes
are supported:

Table B.30 Connection Object Instance 4 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant

1=configuring
3=established

4=timed out

2

Get

Instance Type

USINT

1=I/O Connection

3

Get

Transport Class Trigger

USINT

0x00 (Cyclic, unacknowledged)

0x03 (Cyclic, acknowledged)

0x10 (COS, unacknowledged)

0x13 (COS, acknowledged)

4

Get

Produced Connection ID

UINT

01101xxxxxx

xxxxxx=node

address

5

Get

Consumed Connection ID

UINT

10xxxxxx101

xxxxxx=node

address

6

Get

Initial Comm Characteristics

USINT

0x02 (acknowledged)

0x0F (unacknowledged)

7

Get

Produced Connection Size

UINT

0 to 8

8

Get

Consumed Connection Size

UINT

0 to 8

9

Get/Set

Expected Packet Rate

UINT

in ms

12

Get

Watchdog Action

USINT

0=transition to timed out

1=auto delete

2=auto reset

13

Get

Produced Connection Path Length

UINT

8

14

Get

Produced Connection Path

21 04 00 25 (assy inst) 00 30 03

15

Get

Consumed Connection Path Length

UINT

8

16

Get/Set

Consumed Connection Path

21 04 00 25 (assy inst) 00 30 03

Advertising