Bulletin 284 CIP Information

C-15

Instance 4 is the Predefined Group 2 Connection Set Change of State/
Cyclic I/O Message Connection. The following Instance 4 attributes
are supported

Table C.36 Connection Object Instance 4 Attributes:

Attribute

ID

Access

Rule

Name

Data
Type

Value

1

Get

State

USINT

0 = non-existent
1 = configuring
3 = established
4 = timed out

2

Get

Instance Type

USINT

1 = I/O Connection

3

Get

Transport Class Trigger

USINT

0x00 (Cyclic,
unacknowledged)
0x03 (Cyclic,
acknowledged)
0x10 (COS,
unacknowledged)
0x13 (COS,
acknowledged)

4

Get

Produced Connection ID

UINT

01101xxxxxx
xxxxxx = node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101
xxxxxx = node address

6

Get

Initial Comm Characteristics

USINT

0x02 (acknowledged)
0x0F (unacknowledged)

7

Get

Produced Connection Size

UINT

0…8

8

Get

Consumed Connection Size

UINT

0…8

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get

Watchdog Action

USINT

0 = transition to timed
out
1 = auto delete
2 = auto reset

13

Get

Produced Connection Path
Length

UINT

8

14

Get

Produced Connection Path

21 04 00 25 (assy inst)
00 30 03

15

Get

Consumed Connection Path
Length

UINT

8

16

Get/Set

Consumed Connection Path

21 04 00 25 (assy inst)
00 30 03