Installation and Wiring

2-21

Terminal Designations

ArmorConnect Cable Ratings

The ArmorConnect power media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C
or STOOW 105 °C 600V - CSA STOOW 600V FT2.

Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media

When using ArmorConnect three-phase power media, only fuses can
be used for the motor branch circuit protective device, for the group
motor installations. The following fuse types are recommended: Class
CC, T, or J type fuses.

Terminal
Designations

Description

Color Code

SM1

Safety Monitor Input

Brown

SM2

Safety Monitor Input

White

A1 (+)

Control Power Input

Brown

A2 (-)

Control Power Common Blue

PE

Ground

Green/Yellow

1/L1

Line Power - Phase A

Black

3/L2

Line Power - Phase B

White

5/L3

Line Power - Phase C

Red

Maximum Ratings

Voltage (V)

480Y/277

Sym. Amps RMS

65 kA

Time Delay Fuse

50 A

Non-Delay Fuse

100 A