4-56

Bulletin 284 Programmable Parameters for Sensorless Vector Controllers

PID Feedback Sel
Valid PID Feedback Sel command for the Bulletin 284 ArmorStart is the following;
2 = Comm Port

Parameter Number

233

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

2

Default Value

0

PID Prop Gain
Sets the value for the PID proportional component when the PID mode is enabled by
Parameter 232 (PID Ref Sel).

Parameter Number

234

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.01

Minimum Value

0.00

Maximum Value

99.99

Default Value

0.01

PID Integ Time
Sets the value for the PID integral component when the PID mode is enabled by
Parameter 232 (PID Ref Sel).

Parameter Number

235

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.0 sec

Maximum Value

999.9 sec

Default Value

0.1 sec

PID Diff Rate
Sets the value for the PID differential component when the PID mode is enabled by
Parameter 232 (PID Rel Sel).

Parameter Number

236

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.01 (1/sec)

Minimum Value

0.00 (1/sec)

Maximum Value

99.99 (1/sec)

Default Value

0.01 (1/sec)

PID Setpoint
Provides an internal fixed value for process setpoint when the PID mode is enabled
by Parameter 232 (PID Ref Sel).

Parameter Number

237

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1%

Minimum Value

0.0%

Maximum Value

10.0%

Default Value

0.0%