Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 104

Advertising
background image

104

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

The legend for the coding pegs showing the peg positions is shown on the lower

left of the adapter base unit and on each I/O termination assembly. The positions

are numbered 1…6. The three coding pegs are lettered A, B, and C with A being

on the top. Each peg, or key, is fitted in the base unit so that the index recess is

next to the relevant numbered position. See

Figure 56

.

Figure 56 - Inserted Coding Pegs

Table 13 - Allocations of Coding Pegs

Application

Key A

Key B

Key C

1715 Adapter Base Unit

1

1

1

1715 Digital Input Termination Assemblies

2

1

1

1715 Analog Input Termination Assemblies (for analog input modules)

2

1

3

1715 Digital Output Termination Assemblies (for digital output modules)

3

1

1

32064-M