Digital output termination assemblies, See page 91 for detailed wiring instructions – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 48

Advertising
background image

48

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Digital Output Termination Assemblies

Digital output termination assemblies support these features:

Provide connections for eight output channels
Industry-standard field device connectors
24V DC operation
Provide a fused field voltage supply to the module

There are two types of digital output termination assemblies:

A 1715-TASOB8DE digital output, 24V DC, 8-channel, simplex TA that

provides termination for 8 digital output channels and mates with a single

1715-OB8DE digital output module

A 1715-TADOB8DE digital output, 24V DC 8-channel duplex TA that

provides fault tolerant operation for 8 digital output channels and mates

with redundant 1715-OB8DE digital output modules

Figure 19 - 1715-TASOB8DE and 1715-TADOB8DE Digital Output Termination Assemblies

See

page 91

for detailed wiring instructions.

32121 -M

TB1

TB2

TB3

TB4

J1

J2

c

c

Ov

CH0 CH1 CH2 CH3 CH4 CH5 CH6 CH7

V1+

Ov V1+

Ov V2+

Ov V2+

FH1

FH2

TEST

Ov V1+ Ov V2+ Ov V1+ Ov V2+

CH0 CH1 CH2 CH3 CH4 CH5 CH6 CH7

TB1 TB2 TB3 TB4

J1

FH1

FH2

1715-TADOB8DE

Digital Output Duplex

Termination Assembly

1715-TASOB8DE

Digital Output Simplex

Termination Assembly

32121-M

32093-M TA

10 A Fuse

Fuse type: Littlefuse Type 451 Omni-Block 10 A, 125V very fast acting fuse. Surface Mount Fuse Block 154 010 for Digital Ouptut Termination Assemblies. Use a pair of

long-nosed pliers for fuse removal and replacement.

Field Connections Entry This Side

Field Connections This Side

Polarization Pins

10 A Fuse

Polarization

Pins

Advertising