Mount i/o expansion cable, Cable assembly – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 70

Advertising
background image

70

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Mount I/O Expansion Cable

The expansion cable assembly connects an I/O base unit to another I/O base

unit or to the adapter base unit. It lets extra I/O to be added at a different

location (for example, on a different DIN rail). The cable is 2 m long and

provides connection for up to 24 I/O modules. The maximum length of an entire

bus, or backplane, (the combination of I/O base units and expansion cables) is 10

m.

The assembly consists of a cable, terminated by multi-way plugs, and a pair of

adapters.

The expansion cable offers these features:

Two-meter cable length
Secure with retaining screws and screw cap screws
Connects all command and response signals and system power
Screened to reduce emissions

For additional information on pin-out and pin allocations, see 1715 Redundant

I/O System Technical Data, publication

1715-TD001

.

Cable Assembly

The cable assembly is made up of a SCSI-3 cable and two ferrites. The ferrites are

snap-on components that reduce resonance emissions.

Fit the ferrites 50 mm (1.97 in.) from each end and secure with cable ties either

side of the ferrites.

Table 9 - Cable Assembly

32080-M

Item

Description

1

SCSI-3 cable

2

Ferrite

3

Cable-tie

Advertising