1715-ob8de digital output module – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 125

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

125

Digital I/O Operation

Chapter 3

1715-OB8DE Digital Output Module

The digital output module interface consists of a combination of digital output

modules and digital output termination assemblies. Each module provides 8

isolated output channels and plugs into a single position of the I/O base unit and

a corresponding termination assembly. Digital outputs can be configured as

simplex or duplex.

The 1715-OB8DE digital output module has a flexible, fail-safe design, with

eight field output channels. The module output can be up to 1A continuous for

each channel.

The 1715-OB8DE digital output module features are as follows:

Eight isolated output channels per module
Fail-safe design and operation
Suitable for simplex and duplex connections for fault tolerant applications
Duplex series output switches with overload protection for each channel
Voltage and current monitoring on each channel with reverse current

protection

Short circuit and open circuit line fault detection
Dual redundant field power feed capabilities without the need for external

diodes

When fitted in duplex configuration, modules can be replaced online

without system interruption

ATTENTION: Maintenance must be performed only by qualifiend personnel,
otherwise, personal injury or death, or damage to the system can result.