D - reconfigure a module online, Use ladder logic to reconfigure an i/o module, Reconfigure a module online – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 285: Appendix

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

285

Appendix

D

Reconfigure a Module Online

Use Ladder Logic to

Reconfigure an I/O Module

If an I/O module supports reconfiguration, you can reconfigure the module via

one of these:

Logix Designer application
A MSG instruction in program logic

Reconfigure a Module via Logix Designer Application

To reconfigure a module, perform this procedure.

1. In the Logix Designer application, right-click a module in the I/O

Configuration tree and choose Properties.

IMPORTANT

Consider these guidelines in SIL 2 applications:
We recommend configuring SIL 2 safety applications offline. Even if the

Logix controller and RSLogix 5000 software allow online SIL 2 configuration

(that is, module interface option changes, import of the Add-On

Instructions, and so forth.) a download to the processor is required.

Enabling SIL 2 on spare modules while online is not supported.
A programming terminal is not normally connected.

ATTENTION: Use care when changing the configuration of an I/O module. You
could inadvertently cause the I/O module to operate incorrectly.