Appendix F SIL 2 Applications Checklist
No.
For Energize-to-action SIL 2 Applications
Fulfilled
Comment
Yes
No
1
If there any safety-related, normally de-energized outputs, have you provided redundant power sources, power
failure warning, and line monitoring?
2
Do energize-to-action configurations conform to the restrictions (defined in this manual) that need to be applied
when using these configurations?
3
For energize-to-action SIL 2 applications, have dual output modules been configured?
Checklist for 1715 I/O Modules