The analog I/O modules and termination assemblies for the 1715 Redundant

I/O System are as follows.

1715-IF16 Analog Input Module

The analog input interface is a combination of input modules and analog input

termination assemblies. The 16-channel analog input module has a flexible and

fail-safe design.

The 1715-IF16 analog input module features are as follows:

Flexible, modular construction for user-configured I/O applications
16-channel connection capability
Suitable for simplex, duplex connections and fault tolerant applications
Independent, galvanically isolated input channels
Built-in diagnostic testing and independent watchdog facility
Module removal and replacement online and, when in Duplex mode, no

interruption of the signal inputs

Module power is produced by the internal isolated power supply from the 24V

DC dual redundant system power inputs. The isolated power supply provides

power to the module and is protected by over-voltage and under-voltage

detection circuits. Supply voltage monitoring initiates a warning signal and

Power-off Protection mode when a power failure is detected.

Internal diagnostics test the module at routine intervals. An independent

watchdog arrangement also monitors the module operation and provides

additional fault containment by activating a shutdown mechanism when a fault is

detected.

Table 19 - Types of ControlLogix Analog I/O Modules and Components

Cat. No.

Description

1715-IF16

16-channel analog input module

1715-OF8I

8-channel analog output module

1715-TASIF16

16-channel analog input simplex termination assembly

1715-TADIF16

16-channel analog input duplex termination assembly

1715-TASOF8I

8-channel analog output simplex termination assembly

1715-TADOF8I

8-channel analog output duplex termination assembly

IMPORTANT

If a fault occurs during normal operation in a duplex configured system, an
input module can be removed and replaced without disrupting the input

signals to a live system.

Advertising