Configure the Redundant I/O System

Chapter 5

3. Click Change.

The Module Definition dialog box appears.

Table 31 - Module Definition Parameters for Digital Input Module Duplex Mode

Parameters

Description

Series

Choose the Series of the module.
Only the series supported by the module are displayed.

Revision

Major: Choose the Revision of the module.
Minor: Sets the module’s minor revision.
The valid range is 1…255. This field is enabled while offline, and while in the Program, Remote

Program, and Remote Run modes.
For SIL 2 application choose version 3.01.07 or later for 1715 I/O modules.

Electronic Keying

Choose the electronic keying you wish to use for the selected module.
Valid values are Compatible Module (default), Exact Match, or Disable Keying. See

Appendix B

.

Connection

Leave as ‘Data’ - Listen Only is not supported.

Redundant

Yes for Duplex mode.
No for Simplex mode.

SIL 2 Safety

Choose No if SIL 2 operation is not required.
Choose Yes to enable SIL 2 operation. The safety pulldown appears only if using Add-on Profile version

2.01.007 or later. Two new tabs are available for SIL 2 configuration if you choose Yes. For information on

SIL 2 configuration, see

Chapter 6

.