Chapter 6
1715 Redundant I/O System in SIL 2 Safety Applications
Check SIL 2 Reset Status
If one of more errors have persisted longer than the Connection Reaction Time
Limit (CRTL), the connection uses safe state values and requires a reset to
recover. When online, the SIL 2 reset status is displayed on the SIL 2 Safety tab
for output modules.
Click Reset to reset the connection and enable the output modules to control
their outputs based on logic. To reset the connection for input modules, create a
reset tag within the Add-On Instruction. See
for details.
View Module Information
The configuration signature displayed on the SIL 2 Safety tab is composed of an
ID number, date and time. The signature is updated whenever the module
configuration is changed. You can use this signature to enforce the use of a
specific configuration within your application. The signature is found in the
CRC member of the module’s SIL 2 configuration tag. This is the only occasion
where this tag should be accessed directly.
If you want to keep a record of the signature, you can click Copy to copy the
signature to the Windows clipboard.
Diagnostic Data
While online, click Diagnostics on the SIL 2 Safety tab to view data on the SIL 2
Safety Diagnostics dialog box, shown below.