Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 216

Advertising
background image

216

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 6

1715 Redundant I/O System in SIL 2 Safety Applications

Each time a valid packet is received from the controller, the output module

resets the CRTL. If the CRTL ever times out, the output module assumes

the fail-safe state.

It is recommended that the CRTL remain at the default of four times the

RPI so that one invalid packet does not put the system into the safe state.

For example, if the RPI = 120 ms, then consider 480 ms as the minimum

CRTL. The information in the next section helps determine the maximum

setting for the CRTL.

Determining the Appropriate CRTL Value

Use the following method to confirm whether the default value is acceptable or

you need to change the CRTL value for your application.

The value of CRTL for the I/O connections is governed by this equation:

where CRTLeuc is the process safety time for the equipment under control (euc).

IMPORTANT

The default fail-safe state for all 1715 modules is de-energized.

EXAMPLE

Consider a system function using one sensor and one actuator

given the following parameters:

CRTLeuc: 10,000 ms
Sensor delay: 250 ms
Time for actuator (an ESD valve) to fully operate: 1750 ms

In this example, the setting of CRTL for the I/O connections is

less than or equal to 3000 ms.

Advertising