Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
Chapter 7
information. The actual process rate is affected by the periodic task rate and
periodic task scan time.
The worst case safety reaction time can be calculated using the formulas shown
below.
For the example below, assume the following:
• 1715 Input Module RPI = 60 ms
• 1715 Output Module RPI = 80 ms
• SIL 2 Task Period = 30 ms
• SIL 2 Task Watchdog = 20 ms
• AOI Module RPI=60 ms
If you are not using COS, the worst case reaction time from input screw terminal
to output screw terminal is equal to 210 ms plus the following:
– Input RPI
– Output RPI
– Add-On Instruction Module RPI/2
– SIL 2 Task Period x 6
– SIL 2 Task Watchdog x 2
Table 48 - Worst Case Reaction Time Calculations
Worst Case Factors
Value
Fixed
Time (ms)
User
Configurable
Time (ms)
Description
1715 Input Module Delay
15
1715 Backplane Rate
65
1715-AENTR Delay
25
Input Data to ControlLogix
COS=NO
1715 Input Module RPI
60
COS = Change of State
COS=YES
Fixed
60
Add-On Instruction Module RPI
AOI Module RPI/2
30
Value entered into the AOI Module_RPI parameter
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
Input data asynchronous to scan
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
SIL 2 task period
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
SIL 2 task period
ControlLogix SIL2 Task Watchdog
SIL 2 Task Watchdog
20
ControlLogix system runs input module AOI and controls requested
output
Assumes requested output in same SIL 2 task as 1715 SIL 2 AOIs
Add-On Instruction Module RPI
AOI Module RPI/2
30
Value entered into the AOI Module_RPI parameter
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
AOIs are timer based; input and output AOI timers can be
asynchronous
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
SIL 2 task period
ControlLogix SIL2 Task Period
SIL 2 Task Period
30
SIL 2 task period
ControlLogix SIL2 Task Watchdog
SIL 2 Task Watchdog
20
ControlLogix system runs output module Add-On Instruction and
places requested outputs in output module raw data
Output Data to 1715-AENTR
1715 Output Module RPI
80
1715-AENTR Delay
25
1715 Backplane Rate
65
1715 Output Module Delay
15