Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 194

194
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 5
Configure the Redundant I/O System
The Configuration tab appears.
10. Click the Limits tab.
Table 37 - Analog Output Configuration Parameters Duplex Mode
Parameters
Description
Channel
Click the channel number to configure parameters for the specified channel (0…15).
Current Range
Displays the current range (0…20 mA) for the channel.
This field is read-only.
Low Signal
Check the Low Signal value for the channel (between 0.0…20.0 mA). The default is
4.0 mA. This value must be less than the High Signal value. Low Signal and Low Engineering values are shown in
pairs.
Low Engineering
Check the Low Engineering value for the channel (between -9999999…99999999). The default is 0.0. Low Signal
and Low Engineering values are shown in pairs.
High Signal
Check the High Signal value for the channel (between 0.0…20.0 mA). The default is 20.0 mA. This value must be
greater than the Low Signal value. High Signal and High Engineering values are shown in pairs.
High Engineering
Check the High Engineering value for the channel (between -9999999…99999999). The default is 100.0. High
Signal and High Engineering values are shown in pairs.
Hold for Initialization
Set the channel to hold, or not change, until initialized with a value within 0.1% of full scale of its current value
when one of these conditions occurs:
• Module initial connection (powerup)
• Module transition from Program mode back to Run mode
• Module reestablishes communication after fault.