Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Appendix B

Electronic Keying

EXAMPLE

In the following scenario, Compatible Keying prevents I/O communication:

The module configuration is for a 1756-IB16D module with module revision 3.3. The physical

module is a 1756-IB16D module with module revision 3.2. In this case, communication is

prevented because the minor revision of the module is lower than expected and is not

compatible with 3.3.

EXAMPLE

In the following scenario, Compatible Keying allows I/O communication:

The module configuration is for a 1756-IB16D module with module firmware revision 2.001.

The physical module is a 1756-IB16D module with module firmware revision 3.002. In this

case, communication is allowed because the major revision of the physical module is higher

than expected and the module determines that it is compatible with the prior major revision.

Module Configuration

Vendor = Allen-Bradley

Product Type = Digital Input Module

Cat. No. = 1756-IB16D

Major Revision = 3

Minor Revision = 3

Physical Module

Vendor = Allen-Bradley

Product Type = Digital Input Module

Cat. No. = 1756-IB16D

Major Revision = 3

Minor Revision = 2

Communication is prevented

Module Configuration

Vendor = Allen-Bradley

Product Type = Digital Input Module

Cat. No. = 1756-IB16D

Major Revision = 2

Minor Revision = 1

Physical Module

Vendor = Allen-Bradley

Product Type = Digital Input Module

Cat. No. = 1756-IB16D

Major Revision = 3

Minor Revision = 2

Communication is allowed