Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 278

Advertising
background image

278

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Appendix C

1715-IB16D Digital Input Module Diagnostics

If 5.1V is present, we know the switch is in the off position. We can enter a range

into the threshold that lets 5.1V to be an off condition. We used 3.0 …6.5V as the

range. So, if the voltage drops below 3.0V, it is considered a wire off. If it goes

above 6.5V, it is considered indeterminate.

6.5

6.0

3.5

3.0

5.1V Falls

Within The

Range