Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
8. Create a tag with the appropriate Add-On Instruction data type for the
Requested Output Data.
9. Enter the module RPI.
To optimize system bandwidth, type the same RPI value from the module
configuration.
Add-On Instruction Scan Times
Safety Reaction Time Calculations
The 1715 AOIs process data at a rate of the module RPI / 2. For example, if the
1715-IF16 RPI = 100ms, the 1715 IF16 AOI will process the most recent packet
every 50ms. This provides a compromise between controller bandwidth (not
processing the packets too often using old data) and overall 1715 screw to screw
performance. Because the 1715 AOIs run on a time basis, the input module AOI
and the output module AOI can be asynchronous. See
Table 47 - Maximum Scan Rates Measured
Module
Add-On Instruction
Scan Rate µs (max measured)
1715-AENTR
AENTR_SIL2
Duplex
455
1715-IB16D
IB16D_Simplex_SIL2
Simplex
340
1715-IB16D
IB16D_Duplex_SIL2
Duplex
378
1715-IF16
IF16_Simplex_SIL2
Simplex
831
1715-IF16
IF16_Duplex_SIL2
Duplex
832
1715-OB8DE
OB8DE_Simplex_SIL2
Simplex
501
1715-OB8DE
OB8DE_Duplex_SIL2
Duplex
541
1715-OF8
OF8I_Simplex_SIL2
Simplex
951
1715-OF8
OF8I_Duplex_SIL2
Duplex
964
N/A
CRC Calculator
N/A
N/A