Requirements for using 1715 i/o modules, Energize-to-action requirements – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 207

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
207
1715 Redundant I/O System in SIL 2 Safety Applications
Chapter 6
For energize-to-action, dual power supplies are required for both the system and
field supplies. The system provides the power supply monitoring, but this needs
to be connected in the application.
Requirements for Using 1715
I/O Modules
You must follow these requirements when using 1715 I/O modules in a SIL 2
application.
The maximum duration for single-channel operation of I/O modules depends on
the specific process and must be specified individually for each application. For
high availability, Rockwell Automation suggests you use two (2)
1715-AENTR adapter modules. If one of the modules faults, adapter modules
can operate in a simplex arrangement up to the duration of the mean time to
repair (MTTR) when used in SIL 2 applications.
Energize-to-action Requirements
Certain applications can require energize-to-action for inputs or outputs or both.
IMPORTANT
• In safety applications, channel discrepancy alarms must be monitored by
the application program and used to provide an alarm to operations
personnel.
• Equipment must be installed and wired in accordance with the product
installation and wiring instructions in this manual.
• For energize-to-action systems, you must follow the additional
requirements on
.
IMPORTANT
Energize-to-action configurations can be used only if the following apply:
• At least two independent power sources must be used for both the system
and field supplies. The system provides the power supply monitoring, but
this needs to be connected in the application. These power sources must
provide emergency power for a safe process shutdown or a time span
required by the application.
• Each power source must feature power integrity monitoring with safety-
critical input read-back into the system controller or implicit power
monitoring provided by the I/O modules. Any power failure must trigger an
alarm.
• Unless provided implicitly in the I/O modules, all safety-critical inputs and
outputs must be fitted with external line and load integrity monitoring and
safety-critical read-back of the line-status signals. Any line or load failure
must trigger an alarm.
• The application program must be designed to shut down energize-to-
action SIL 2 safety instrumented functions if a faulty simplex adapter or
output module has not been replaced within the mean time to repair
(MTTR).
• For SIL 2 high demand, energize-to-action applications, you must use two
output modules.
In cases where one or more outputs is used in an energize-to-action
configuration, all the specific requirements above must be implemented for all
associated inputs.