Chapter 6

1715 Redundant I/O System in SIL 2 Safety Applications

Analog Output Modules

The analog output module can be used in applications where the output current

is in the range 4…20 mA during normal operation including trip/action value

and where 0 mA is the fail safe value. In these applications, one 1715-OF8I

output module is sufficient for SIL 2 requirements, two modules provide a 1oo2

level.

The analog output module is rated at SIL 2 as a fail-safe simplex module and

when used in a 1oo2 configuration as a duplex module with these features:

Commanded values and scaling factor

The fail-safe lowest commanded value irrespective of the scaling factor is

0 mA. The application cannot change the scaling factor; it can only be

changed by an online update.

Fail-safe guard band

The fail-safe guard is 1% (0…2 mA) and not user-configurable.

Reaction to Faults

If an output module faults, the following status information is reported:

Module presence
Module health and status
Channel health and status
Field faults
An echo of the front panel indicators for each module

If any of the following internal conditions exist, the output module fails safe:

An internal software error is detected
A power feed combiner over-temperature condition is detected