Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 162

162
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 5
Configure the Redundant I/O System
4. Click Change.
The Module Definition dialog box appears.
5. Click OK.
Table 24 - Module Definition Parameters
Parameters
Description
Series
Module series letter.
Revision
Major: Choose the revision of the module.
Minor: Set the module’s minor revision. This field is enabled while offline, and while in the Program, Remote
Program, and Remote Run modes. It appears dimmed when in Run mode, or when electronic keying is set to
Disable Keying.
For SIL 2 applications, choose version 2.01.07 or later for 1715-AENTR modules.
Electronic Keying
Electronic Keying, see
Appendix B.
Valid values are Compatible Module (default), Exact Match, or Disable Keying.
Connection
Leave as ‘Data’ - Listen Only is not supported.
Redundant
Always Yes.
SIL 2 Safety
Choose No if SIL 2 operation is not required.
Choose Yes to enable SIL 2 operation. The safety pull-down menu appears only if using Add-on Profile version
2.01.007 or later. Two new tabs are available for SIL 2 configuration if you choose Yes. For information on SIL 2
configuration, see
.
Chassis Size
Choose the chassis size you want to use: 5,8,11,14,17,20,23,26.
The chassis size is a function of the number of bases installed in your system, which come in either groups of three
slots per base for I/O bases; and two slots per base for the redundant adapter base.
All slots in the chassis do not have to be populated.
To extend the size of a chassis, its size must be consistent with the number of base slots used. The minimum
chassis size is 5 slots, built from one 2-slot adapter base and one 3-slot I/O base.