Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

93

Installation Instructions

Chapter 2

Field Loop Circuits for Digital Outputs

The field loop circuit for a digital output is shown in

Figure 43

.

Figure 43 - Digital Output (simplex or duplex) Field Loop Circuit

IMPORTANT

The field power 5A fuses comply with UL508 requirements. The 5A fuses are
No. 396/TE5 5A time lag fuse; UL 248-14, 125 V,T Leadfree; manufactured by

Littlefuse.
You can use Class 2 power supplies for the +24V DC field voltage instead of

the two 5A fuses. Class 2 is defined by the NEC as providing less than 100

watts (at 24V).

When digital output modules are configured as a redundant pair, the

minimum load current required for channels with line monitoring is 20 mA.

DC

DC

33002-M

Important: For inductive loads, a back EMF protection diode

is fitted at the load.