Sil 2 add-on instructions overview, Chapter 7, Chapter – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 223

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

223

Chapter

7

Using SIL 2 Add-On Instructions with 1715

Redundant I/O Modules

SIL 2 Add-On Instructions

Overview

Topic

Page

SIL 2 Add-On Instructions Overview

223

SIL 2 Check Data

227

Add-On Instruction Inputs

227

Add-On Instruction Outputs

228

Download and Import the Add-On Instructions

229

Configure an Input Module Add-On Instruction

234

Configure an Output Module Add-On Instruction

238

Using the Add-On Instruction Data Tags in an Application Program

242

Performing a SIL 2 Reset

243

IMPORTANT

To achieve SIL 2 with 1715 I/O modules in a ControlLogix system, you must use
these Add-On Instructions. The SIL 2 Add-On Instructions verify the validity of

data transferred between the ControlLogix controller and the 1715 modules via
the 1715-AENTR adapter. See

Download and Import the Add-On Instructions

on page 229

.

IMPORTANT

As you proceed with this chapter, be aware that when using the 1715 SIL 2
Add-On Instructions, you should not read inputs directly from the input table,
nor should you write directly to the output tags. You will read inputs from an

Add-On Instruction tag called ‘reconciled input data,’ and write outputs to an
Add-On Instruction tag called ‘requested output data.’

IMPORTANT

There is an Add-On Instruction required for the 1715-AENTR, as well. The status

data from the 1715-AENTR must be validated by using this Add-On Instruction.

IMPORTANT

You cannot view the logic of each Add-On Instruction because they are source
protected.