Troubleshooting faults – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 251

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

251

Status Indicators

Appendix A

Troubleshooting Faults

Follow this troubleshooting procedure to diagnose field faults.

1. Note the affected channel as a field fault can indicate that there is a blown

fuse on an input channel.

2. Check the input field connections to the faulty channel to find the source

of the over voltage that caused the fuse to blow.

3. After you have removed the source of the over voltage, replace the blown

fuse by following these steps.

The fuse can be changed with the termination assembly still installed. You

do not have to remove it.
a. Lift the plastic cover that covers the fuses.
b. Use a fuse removal tool to lever the fuse out of the fuse holder and

replace the fuse.

You can use these types of replacement fuses.

c. Close the plastic cover.

Component

Fuse Type

Analog Input Termination Assembly

Littlefuse No. 396/TE5 50 mA time lag fuse; UL 248-14,

125 V, T Leadfree

Digital Input Termination Assembly

Littlefuse No. 396/TE5 50 mA time lag fuse; UL 248-14,

125 V, T Leadfree

Digital Output Termination Assembly

Littlefuse Type 451 Omni-Blok 10 A, 125 V very fast acting

fuse. Surface mount fuse block 154 010