Features common to all analog i/o modules, Removal and insertion under power (riup), Module fault reporting – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual
Page 144

144
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 4
Using 1715 Analog I/O Module Features
Features Common to All
Analog I/O Modules
The features that are common to all 1715 and ControlLogix analog I/O modules
are listed in
. The features are described later in this section.
Removal and Insertion Under Power (RIUP)
All 1715 I/O modules can be inserted and removed from the chassis while power
is applied. This feature allows greater availability of the overall control system
because, while the module is being removed or inserted, there is no additional
disruption to the rest of the controlled process.
Module Fault Reporting
The 1715 analog I/O modules provide hardware and software indication when a
module fault has occurred. Each module has a status fault indicator and
the Logix Designer application graphically displays this fault and include a fault
message describing the nature of the fault. This feature lets you determine how
your module has been affected and what action must be taken to resume normal
operation.
Table 21 - Performance Criteria for the Analog Output Module
Attribute
Value
Data Input value least significant bit (control)
0.98 µA
Data Output value least significant bit (monitor)
3.9 µA
Channel Measurement Error at 25 °C (77 °F) ± 2 °C (±3.6 °F)
After 1 year at 40 °C (104 °F)
After 2 years at 40 °C (104 °F)
After 5 years at 40 °C (104 °F)
0.30% + 10 µA
0.35% + 10 µA
0.44% +10 µA
Temperature drift
(0.01% + 0.1 µA) per °C
ATTENTION: Maintenance must be performed only by qualifiend personnel,
otherwise, personal injury or death, or damage to the system can result.
Table 22 - Common Analog I/O Module Features
Feature
Page