The adapter base unit is always the leftmost base unit in the connection chain.
The total length of the base unit backplane length, including all expansion cables
cannot exceed 10 m (32.81 ft).
A base slot (adapter or I/O) consumes an address whether it is full or empty. The
first adapter in the pair occupies slot 0 and is on the left, the second adapter
occupies slot 1 and is on the right. Only adapters can occupy the slots of the
adapter base.
An adapter base unit can support up to 8 I/O base units (up to 24 I/O modules)
on its right side.
Module positions within the I/O base units are numbered from 2…25, the
leftmost position being slot 2.
The total number of slot positions in the system is 26; 0…1 are occupied by
adapters and 2…25 are occupied by I/O modules.
Expansion cables can be used to connect base units, as shown here.