Redundant I/O System Diagnostics

Diagnostic Features

Many of the diagnostic functions associated with an analog module are provided

by proxy by the adapter. These tables summarize the functions for each module

type.

Topic

Page

Diagnostic Features

245

Table 49 - 1715-AENTR Adapter Module Diagnostic Features

Feature

Description

Redundancy level

Duplex only.

Redundancy status

The status of each module of a duplex pair is available in the input tag.

Communication diagnostics

Various communication diagnostic information is available through the input tag. For each physical

Ethernet port, this includes: Link status, duplex setting, speed and auto-negotiation status. For the

module, this includes: CIP on EtherNet/IP timeout count, CIP on EtherNet/IP connection count, CIP on

EtherNet/IP network Lost Packets count, TCP Connection count and CPU utilization.

Table 50 - 1715-IB16D Module Diagnostic Features

Feature

Description

Redundancy level

Simplex or duplex.

Redundancy status

The status of each module of a duplex pair is available in the input tag.

Change-of-state transport

The connection trigger for the discrete modules is to be change-of-state.

Points that trigger production

The trigger for change-of-state production is selectable on a point basis for values and on a module

basis for diagnostics.

Open wire detection

With an appropriate end-of-line device installed and the open wire detection diagnostic enabled, a

fault is indicated when an open wire condition is detected. The fault indication is reset when the

open wire condition no longer exists. Open wire detection can be disabled to prevent unused points

from indicating faults.

Short circuit detection

With an appropriate end-of-line device installed and the short circuit detection diagnostic enabled, a

fault is indicated when a short circuit is detected. The fault indication is reset when the short is

removed.

Overload protection

User-serviceable fuses are included in the termination assembly.

Diagnostic latch

When latching is enabled, diagnostic alarms are latched until they are reset. This aids in detecting

intermittent issues. For input modules, latch reset occurs only through messaging.

Configurable thresholds

To allow flexibility in the use and choice of end-of-line devices, the thresholds for detection of inputs,

short circuits, and open wires are user selectable.