Page 91

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
91
Installation Instructions
Chapter 2
Figure 39 - Connections to 1715-TASOB8DE and 1715-TADOB8DE Digital Output Termination
Assembly 8-channel Simplex/Duplex
Apply a minimum tightening torque of 0.5 N•m (0.37 lb•ft) to the terminal
screws.
The 24V DC field voltages VFIELD 1 and VFIELD 2, used by the output
module for the output field voltages, are connected at the terminal blocks and fed
via two replaceable 10 A fuses, F1 and F2. These fuses give protection for the
output module against field faults. Field OV (VFIELD RTN) is also routed from
the output module connectors to the terminal block.
Figure 40 - 1715-TASOB8DE Digital Output Simplex Termination Assembly Connections
OV
OV
OV
V1 +
+
V2
V1 +
V2 +
OV
To
Next
TA
(if fitted)
TB1
TB2
TB3
TB4
CH0
CH2
CH4
CH6
CH1
CH3
CH5
CH7
32105-M DO TA Field Wiring
VFIELD1+24V DC
VFIELD2+24V DC
VFIELD RTN OV
DO CH0
DO CH1
DO CH2
DO CH3
DO CH4
DO CH5
DO CH6
DO CH7
F2
F1
Digital Output Module
Fail Safe Channel
Array
32103-M DO Simplex Output
Connections