Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

119

Installation Instructions

Chapter 2

The following status indicators light depending on which module you are

installing. This is a quick installation reference. For more detailed status indicator

information, see

Appendix A

.

7. Turn the locking screw on the front of the module a 1/4 turn clockwise to

lock, referring to

page 110

.

The 1715-IB16D digital input module’s Redundancy Status indicator

shows RED when the screw is locked.

The 1715-IF16 analog input module’s Redundancy Status indicator

shows RED when the screw is locked.

The module enters its start-up sequence. This takes approximately 3

seconds.

If the module is the first module in a TA group with a running adapter, it

displays the following status indicators. See

Table 16

.

Table 15 - Start-up Sequence

1715-IB16D, 1715-OB8DE, 1715-IF16, and 1715-OF8I Modules
Indicator

Status

Module Status

Green

Redundancy Status

Off

Network Status

Red

Channel 0…7, 8…15

Off

Table 16 - First Module in TA Group

1715-IB16D, 1715-OB8DE, and 1715-IF16

Modules

1715-OF8I Module

Indicator

Status

Indicator

Status

Module Status

Green

Module Status

Green

Redundancy Status

Green

Redundancy Status

Red to steady green

Network Status

Amber

Network Status

Amber

Channel 0…7, 8…15

Off

Channel 0…7

Off